MP3 20-75
- Gas: Natural or propane
- Blast mode rate (MBH): 85
- Standard modulating range (BTU/h): 65,000-75,000
- Length: 26'-5"
- Weight: 145
- Combustion chamber: aluminized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 12'-20'
MP3 20-80
- Gas: Natural or propane
- Blast mode rate (MBH): 85
- Standard modulating range (BTU/h): 65,000-80,000
- Length: 26'-5"
- Weight: 145
- Combustion chamber: aluminized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 12'-20'
MP 25-80
- Gas: Natural or propane
- Blast mode rate (MBH): 85
- Standard modulating range (BTU/h): 65,000-80,000
- Length: 26'-5"
- Weight: 145
- Combustion chamber: aluminized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 12'-20'
MP3 30-80
- Gas: Natural or propane
- Blast mode rate (MBH): 85
- Standard modulating range (BTU/h): 65,000-80,000
- Length: 31'-5"
- Weight: 145
- Combustion chamber: aluminized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 12'-20'
MP3 30-115
- Gas: Natural or propane
- Blast mode rate (MBH): 120
- Standard modulating range (BTU/h): 85,000-115,000
- Length: 31'-5"
- Weight: 160
- Combustion chamber: aluminized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 14'-22'
MP3 40-80
- Gas: Natural or propane
- Blast mode rate (MBH): 85
- Standard modulating range (BTU/h): 65,000-80,000
- Length: 41'-1"
- Weight: 190
- Combustion chamber: aluminized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 12'-20'
MP3 40-115
- Gas: Natural or propane
- Blast mode rate (MBH): 120
- Standard modulating range (BTU/h): 85,000-115,000
- Length: 41'-1"
- Weight: 190
- Combustion chamber: aluminized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 15'-25'
MP3 40-150
- Gas: Natural or propane
- Blast mode rate (MBH): 155
- Standard modulating range (BTU/h): 110,000-150,000
- Length: 41'-1"
- Weight: 190
- Combustion chamber: titanium stabilized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 15'-28'
MP3 50-115
- Gas: Natural or propane
- Blast mode rate (MBH): 120
- Standard modulating range (BTU/h): 85,000-115,000
- Length: 50'-9"
- Weight: 235
- Combustion chamber: aluminized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 15'-28'
MP3 50-150
- Gas: Natural or propane
- Blast mode rate (MBH): 155
- Standard modulating range (BTU/h): 110,000-150,000
- Length: 50'-9"
- Weight: 235
- Combustion chamber: titanium stabilized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 17'-30'
MP3 50-200
- Gas: Natural or propane
- Blast mode rate (MBH): 200
- Standard modulating range (BTU/h): 135,000-200,000
- Length: 50'-9"
- Weight: 235
- Combustion chamber: titanium stabilized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 19'-37'
MP3 60-150
- Gas: Natural or propane
- Blast mode rate (MBH): 150
- Standard modulating range (BTU/h): 110,000-150,000
- Length: 60'-5"
- Weight: 265
- Combustion chamber: titanium stabilized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 17'-32'
MP3 60-200
- Gas: Natural or propane
- Blast mode rate (MBH): 200
- Standard modulating range (BTU/h): 135,000-200,000
- Length: 60'-5"
- Weight: 265
- Combustion chamber: titanium stabilized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 19'-37'
MP3 70-200
- Gas: Natural or propane
- Blast mode rate (MBH): 200
- Standard modulating range (BTU/h): 135,000-200,000
- Length: 70'-1"
- Weight: 300
- Combustion chamber: titanium stabilized steel
- Radiant emitter tubes: 16 ga. 4” aluminized steel
- *Mounting heights: 19'-42'
* Mounting heights are provided as a guideline. Actual conditions may dictate variations from the above data. Always maintain the published clearances to combustibles. Not for residential use.
Recommended clearance to combustibles
MP (20, 25, 30, 40)-75, 80
Mount angle |
Sides | Top | Below |
0° |
14" | 6" | 66" |
45° | Front 39" Back 8" | 10" | 66" |
0° 1 side shield | Front 29"
Back 8" | 6" | 66" |
0° 2 side shields | 16" | 6" | 66" |
0° 20 ft from burner | 7" | 6" | 30" |
MP (30, 40, 50)-115
Mount angle |
Sides | Top | Below |
0° |
20" | 6" | 76" |
45° | Front 58" Back 8" | 10" | 76" |
0° 1 side shield | Front 42"
Back 8" | 6" | 76" |
0° 2 side shields | 20" | 6" | 76" |
0° 20 ft from burner | 7" | 6" | 30" |
MP (40, 50, 60)-150
Mount angle |
Sides | Top | Below |
0° |
24" | 6" | 83" |
45° | Front 58" Back 8" | 10" | 83" |
0° 1 side shield | Front 42"
Back 8" | 6" | 83" |
0° 2 side shields | 23" | 6" | 83" |
0° 20 ft from burner | 11" | 6" | 46" |
MP (50, 60, 70)-200
Mount angle |
Sides | Top | Below |
0° |
41" | 6" | 100" |
45° | Front 63" Back 8" | 10" | 100" |
0° 1 side shield | Front 54"
Back 8" | 6" | 100" |
0° 2 side shields | 30" | 6" | 100" |
0° 20 ft from burner | 11" | 6" | 50" |
Clearances published in MP Series manual and on warning label supersede data shown on this page. Reference MP Series
installation manual for complete information.
Heaters mounted on an angle between 0º and 45º must maintain clearances posted for 0º or 45º, whichever is greater.