DSRF 30 models
DSRF-30-65
- Gas: Natural or propane
- BTU/h high fire: 65,000
- BTU/h low fire natural: 50,000
- Housing: aluminum
- Length: 16'-4"
- Weight: 170 lbs
- Vented
- Certified for commercial indoor & outdoor use
- *Mounting heights: 9'-16'
- Approx. area heated: 26'x12'
DSRF-30-80
- Gas: Natural or propane
- BTU/h high fire: 80,000
- BTU/h low fire natural: 52,000
- Housing: aluminum
- Length: 16'-4"
- Weight: 170 lbs
- Vented
- Certified for commercial indoor & outdoor use
- *Mounting heights: 9'-16'
- Approx. area heated: 26'x12'
DSRF 35 models
DSRF-35-65
- Gas: Natural or propane
- BTU/h high fire: 65,000
- BTU/h low fire natural: 50,000
- Housing: aluminum
- Length: 21'-10"
- Weight: 170 lbs
- Vented
- Certified for commercial indoor & outdoor use
- *Mounting heights: 9'-16'
- Approx. area heated: 26'x12'
DSRF-35-80
- Gas: Natural or propane
- BTU/h high fire: 80,000
- BTU/h low fire natural: 52,000
- Housing: aluminum
- Length: 16'-4"
- Weight: 170 lbs
- Vented
Certified for commercial indoor & outdoor use - *Mounting heights: 9'-16'
- Approx. area heated: 26'x12'
* Mounting heights are provided as a guideline. Actual conditions may dictate variations from the above data. Always maintain the published clearances to combustibles. Not for residential use.
Clearance to combustibles
DSRF
(30, 35) 65,80
Mount
angle | Sides | Top | Ends. Below |
0° | 25" | 6" | Ends 12" Below 60" |
30° | Front 36"
Back 10" | 9" | Ends 12"
Below 47" |
DSRF
(30, 35)-100
Mount
angle | Sides | Top | Ends. Below |
0° | 25" | 6" | Ends 12" Below 77" |
30° | Front 45"
Back 10" | 9" | Ends 12"
Below 64" |
Clearances published in DSRF Series manual and on warning label supersede data shown on this page. Reference DSRF Series installation manual for complete information.
Heaters mounted on an angle between 0º and 30º must maintain clearances posted for 0º or 30º, whichever is greater.